Intelligent Motor Protection Controller

VR-810MRC-3

VR-810MRC-3.jpgStandard features

Have such protection functions as short circuit protection, stalling protection, overload protection, earthing protection, open phase/unbalance protection, under load protection, TE curve protection, under voltage / over voltage protection, No-voltage restart , start overtime protection, power loss protection, external failure protection, current leakage protection (with external CT), electric dazzling protection;

Measure such electrical parameters as three-phase current, zero-sequence current, three-phase current unbalance factor, three-phase voltage, zerosequence voltage, three-phase voltage unbalance factor, active/reactive power, power factor and frequency; realize comprehensive protection for motor, and record the protection events;

Active electric energy (kWh), reactive electric energy (kvarh);

Protection method: relay protection output method, realizing protection function by means of relay normal closed contact (hard closed contact) placing in secondary circuit;

Wide range AC/DC power supply: AC/DC 110V~250V;

1-channel RS-485 communication interface, Modbus-RTU communication protocol; 8-channel switching value remote signal input: among them, D17 has failure intertripping function, 4-channel relay output;

Integrated measurementand SOE records, real-time reading via communication interface; the protection parameters can be set through display unit and communication software;


Optional features

Extended display unit: real-time display of power measurement, on-site setting of parameters

Chinese LCD display unit PDM-810DSC-2 (DSC2)

Double RS-485 communication interface (C)

Profibus-DP communication interface (DP)

DeviceNet communication interface (DE)

No-voltage restart (Z)

Connected to zero-sequence/leakage CT input, measure zero-sequence/ leakage current (Y1A/Y50)

There are two current input modes available for user's choice.

1. Special small CT input (MT optional): less than 15A( MT25), 15A-60A(MT100 )、30A-110A( MT150)、60A-150A(MT250 )

2. In case of more than 150A, adopt standard CT (1A/ 5A)

Select one from DP, DE and double RS-485 communication functions


Overall Dimensions:

8-VR-810MRC-3.jpg